Product Description
Everexceed 110V400A Uxcel Series Single Phase or Three Phase Thyristor
Details:
EverExceed offers highly reliable and rugged Thyristor Industrial Battery Charger solutions for all DC Power Supply applications. The EverExceed uXcel range industrial battery charger is the flagship charger of EverExceed Industrial Power solutions. It integrates proven design topology with the latest advanced digital control technology to control the 6-pulse thyristor bridge rectifier and provide the most reliable and trouble-free performances in any electrical and industrial environments.
Features
Features:
• High Reliability and High MTBF - Robust and unique design allows the charger to continuously operate at full load at a 40°C ambient temperature. Natural ventilation and cooling are available on most of the range. Precisely compensate adjustable temperature.
• Versatile constant voltage and constant current charging modes.
• Enhanced Robustness - Mechanical design to withstand vertical and horizontal acceleration stress up to 0.5g as standard.
• Leading Technology - Phase-controlled Thyristor technology. The embedded micro-computer controller processes signals 10 times faster than standard analog methods.
• Flexible maintenance and Reduced MTTR - The design make it easy for front-access to all vital modules of the charger.
• Long design life up to 20+ years - system design life up to 20+ years in continuous operation under the condition of appropriate maintenance.
• Isolation transformer.
- Multilingual digital graphic display with embedded event log.
- Full compatibility with lead-acid and nickel- cadmium batteries, sealed or vented.
• Large LCD display- User-friendly operation with large LCD display, touch screen optional with the choices of 8 languages made to order.
• Smart Communication and Remote Monitoring- Through isolated RS232, RS485, and Ethernet. Full data logging.
Application:
- Oil & gas offshore & onshore
- Refining petro chemicals
- Telecom
- Transportation (Rail & Aeronautic)
- Power generation, transmission & distribution
-
Product Parameters
INPUT |
AC voltage |
|
·Single phase |
1×230V(220,240) |
·Three phase |
3×400V(380,415) |
Input voltage tolerance |
±10% |
Input Wiring |
3 Phase 3 Wirse or 3 Phase 4 Wires |
Input frequecny |
50Hz(60Hz) |
Input frequecny tolerance |
±5% |
Input Protection |
Thermic Magnetic Overcurrent protection via MCCB |
OPTIONS |
Rectifier |
Other input voltage(1×110 to 3×690VAC) |
Harmonic filter for THDi≈15% |
Blocking diode |
Surge and Lightning protections |
Voltage ripple filter |
Bettery |
Battery circuit protection box |
Battery reversed polarity detection |
Battery low-voltage disconnection contactor (LVD) |
Battery room temperature sensor |
Battery cabinet / rack |
Battery monitoring system |
System |
Parallel configurations |
Dropping diodes/DC-DC converter |
Earth fault monitoring |
Internal cabinet lighting |
Anti-condensation heater |
Output breaker |
Front-panel analog meters/digtal meters |
DC distribution |
Temparature compensation |
AC high and AC low alarm/protection |
DC high and DC low alarm/protection |
AC fault alarm |
LED test function |
Mechanical |
Other frame colour |
Up to IP55 external |
Plate thickness |
Specified cabinet identification (tag, nameplate) |
Communication |
Modbus TCP/IP |
modbus RTU(RS485) |
DNP3.0 protocol |
Volt-free contacts |
Transducers 4-20mA |
Remote monitoring |
|
|
OUTPUT |
Nominal DC voltage |
24/48/110/125/220/240/400 |
Output voltage range |
0-1.5×nominal voltage (adjustable) |
Nominal DC current |
10-1500A |
Output current range |
0-1.1×nominal current(adjustable) |
Voltage stability |
±1% in float mode, input within tolerance |
Voltage ripple |
1% RMS(with battery connected) |
Current Limitation |
Battery current limitation can be adjusted |
Filtering |
L-C Filter |
Output Protection |
Short Circuit, NH Fuse and Overvoltage protection |
BATTERY |
Type |
Lead acid or nickel cadmium,
vented or recombination and Lithium battery |
COMMUNICATION |
Communication |
RS232, Modbus RTU |
GENERAL DATA |
Operating temperature |
0 to 50 °C |
Storage temperature |
-20 to +70 °C |
Relative humidity |
< 95 % non condensing |
Operating altitude |
1000 m max without derating |
Cooling |
Fan cooling or Natural cooling according to rating |
Efficiency |
90% according to rating |
External protection |
IP20 |
Noise
(at 1m in front of the unit) |
55 - 65 dB according to rating |
Cabinet color |
RAL 7035 |
Dimensions |
Varying according to ratings & options |
STANDARDS |
IEC60146-1-1:2009 |
Semiconductor converters - Specification of basic requirements |
IEC62040-1:2008+AMD1:2013 |
Uninterruptible power systems (UPS) - Part 1-2: General and safety requirements for UPS in restricted access locations |
IEC62040-2:2006 |
Uninterruptible power systems (UPS) - Part 2: Electromagnetic compatibility (EMC) requirements |
IEC61439-1:2011 |
Low voltage switchgear and controlgear assemblies - Part 1: General rules |
IEC60529:1989+ AMD1:1999 |
Degrees of protection provided by enclosures (IP Code) |
IEC60076-11:2004 |
Power transformers - Part 11: Dry type transformers |
European Directives |
Low voltage directive: 2006/95/EC and 2014/35/EU
EMC directive: 2004/108/EC and 2014/30/EU
CE Mark |
|
Certifications