EverExceed Long Life 12V 100ah Front Terminal Battery for Solar /UPS/ Telecom System
Product Introduction:
The extremely powerful, compact AGM batteries of EverExceed front access FT Range are an ideal energy source for durability in Telecommunications and Electric Utility applications. These batteries provide high performance and reliability in long duration discharge applications. Our development team combines the market's demand with design optimization, precision component selection and state of the art manufacturing process to produce the most cost effective battery solution for today's applications.
Electrical Specifications:
Cells Per Unit |
Voltage Per Unit |
Weight |
Electrolyte |
Maximum discharge current |
Short Circuit Current |
Ohms Imped 60 Hz(Ω) |
6 |
12.84 |
38.0lbs 17.3kg |
SG = 1.300 |
349 Amps |
1900 Amps |
0.00553 |
Capacity |
56.1 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F). 55.3 Ah @ 8 hr. rate to 1.75 volts per cell @ 20°C (68°F). 168 Watts per all at the 15 minute rate to 1.67 volts per cell @ 20°C (68°F). |
Applicable Operating Temperature Range |
-40°C (-40°F) to +70°C (+158°F). |
Ideal Operating Temperature Range |
+20°C (+68°F) to +28°C (+82.4°F ). |
Floating Charging Voltage |
13.5 to 13.8 VDC/unit Average at 25°C (77°F). |
Recommended Maximum Charging Current Limit |
0.2C20 amperes (12.8 amperes @ 100% depth of discharge) @ 20 hr. rate to 1.75VPC. |
Equalization and Cycle Service Charging Voltage |
14.1 to 14.4 VDC/unit Average at 25°C (77°F). |
Maximum AC Ripple (Charger) |
0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Maximum voltage allowed = 1.4% RMS (4% P-P). Maximum current allowed = 3.20 amperes RMS (C/20) to 1.75VPC. |
Self Discharge |
EverExceed FT AGM Range batteries may be stored for up to12 months at 20°C~25°C (68°F~77°F) and then a freshening charge is required. For higher temperatures the time interval will be shorter. |
Accessories |
Inter unit connectors racks and cabinet systems are available. |
Terminal: Inserted |
Threaded copper alloy insert terminal |
Terminal Hardware Initial Torque: Inserted Terminal |
9 NM |
Technical features:
• Virgin Pure Lead Tin and thick positive plate technology design for maximum service float life - 15 years design life @ 20˚C(68˚F);
• Valve regulated lead acid battery (VRLA);
• Optimized high-compression Absorbed Glass Mat (AGM) materials significantly enhance performance and reliability, greater than 99% recombination efficiency;
• Advanced triple stage unique terminal sealing design to ensure leak free operation;
• Operates at a low internal pressure;
• Heavy duty M6 / M8 Female copper plated terminals provide maximum performance and easy installation, reduce maintenance and increase safety;
• Advanced lead tin low-calcium alloy, reduces grid corrosion and promotes long battery life;
• Designed to withstand extreme temperature degrees and performance without degradation;
• Over-sized, through the partition inter-cell welds provide low resistance connections, with minimum power loss;
• Multi-cell design for ease of installation and maintenance;
• Horizontal or vertical operation.
• Proprietary Fixed Orifice Plate Pasting technology applying active materials on both sides of the grid for consistent cell-to-cell performance, higher capacity and uniform grid protection.
Applications:
• Telecommunications
• Distributed Power
• Cellular Radio
• Broadband
• UPS
• Switchgear Control Power
Why us? |
|
Reasons you would prefer to buy this power supply products from us |
Service |
RMA(24/7 pre-sales and after-sales support),OEM,ODM |
Quality |
Highly reliable quality guaranteed by Varta production equipment, German technology, European raw materials |
Warranty |
Standard 2 years, 5+ years upon request |
Price |
Competitive factory Price! Cut down the cost you paid to the middle man |
Professional |
Founded in 1985, 30+ years battery manufacturing experience |
Production capacity |
3,500,000KVAh per year |
Reliable |
Two R&D centers;
Three major production bases;
Global 500+ dealers/ agents;
Global 100+ offices;
Business coverage 65+ countries around the world |
Shipping & Payment |
Payment |
T/T, L/C , Cash, Western Union etc.(flexible payment term can be discussed) |
Port |
Normally Shenzhen China (any sea port upon request) |
Delivery |
By sea/air/trian/truck transportation |
Delivery time |
Normally 4 weeks ex factory excluding shipping. |
Packing: |
Pack in carton box then pallet (wooden box) |
FAQ:
Ø Q1. Can your battery be delivered by sea and air?
A: Yes, our batteries can be delivered both by sea and by air. We have MSDS, test report for safe transport as non-dangerous products.
Ø Q2. Can I put my logo on the battery?
A: Yes, you can print your logo on our batteries when you order reach 20ft container quantity. If not, price will be negotiated.
Ø Q3. Can I fast charge my battery?
A: Fast charging is not recommended as ifs harmful for the battery.
ØQ4. Can I do a partial replacement of my batteries?
A: Partial battery replacement of lead acid battery banks is not recommended.
Ø Q5. How about your delivery time usually?
A: About 7 days for stock products, around 20 days for half container products, 30 days for 20ft full container products.
Ø Q6. Are you a battery manufacturer, and do you produce the plate by yourself ?
A: Yes, we are a professional battery manufacture in Guangdong Province, China. And we produce plates by ourselves.
Ø Q7. What certificate your company have?
A: ISO 9001, ISO 14001, OHSAS 18001, CE, UL, IEC 61427 test report, Patent for gel technology and other Chinese honor.
Ø Q8.What is your warranty time for VRLA battery ?
A: It depends on battery capacity, depth of discharge, and battery usage. Please kindly contact us for accurate information based on detailed requirements.
Ø Q9. Why battery has different capacity at different hour rate?
A: The capacity of a battery, in Ahs, is a dynamic number that is dependent on the discharge current. For example, a battery that is discharged at 10A will give you more capacity than a battery that is discharged at 100A. With the 20-hr rate, the battery is able to deliver more Ahs than with the 2-hr rate because the 20-hr rate uses a lower discharge current than the 2-hr rate.
Ø Q10. What is the shelf life of VRLA battery and how to maintain the battery?
A: The limiting factor of battery's shelf life is the rate of self-discharge which itself is temperature dependent. VRLA batteries will self-discharge less than 3% per month at 77° F (25° C). VRLA batteries should not be stored for more than 6 months at 77° F (25° C) without recharged. If in hot temperature, recharge it every 3 month. When batteries are taken out of long storage, it is recommended to recharge before use.
Ø Q11. How does your factory control the quality?
A: We Adopt ISO 9001 quality system to control the quality. We have Incoming Quality Control (IQC) department to test and confirm raw material meets high quality producing requirements, Production Quality Control (PQC) department contains The first Inspection, In-process quality control, acceptance inspection and full inspection, Outgoing Quality Control (OQC) department confirm no defective batteries come out from the factory.