Nominal Voltage |
12V |
24V |
48V |
110V |
220V |
400V |
Nominal current |
25-1500A |
25-1500A |
25-1500A |
16-1500A |
16-1500A |
16-1000A |
Input supply |
Single phase 120V/220V/230V/240V,three phase 208V/380V/400V/415V/480V |
Input voltage/Frequency tolerance |
± 10%, 50/60Hz ± 5% |
Output voltage |
1.8-18V |
3.6-36V |
7.2-72V |
16.5-165V |
33-330V |
60-600V |
Voltage ripple |
<2% specified full load and without battery connected |
Static voltage regulation |
± 1% for 0-100% load variation, ± 10% AC input voltage variation and 5% AC input frequency variation |
Dynamic voltage |
5% for load variation of 10% to 100% to 10% |
Current regulation |
1% |
Protection |
Input circuit breaker, Charger output fuse/Circuit breaker*, Charger current limit, Dual battery limit, AC surge supression*, Short circuit protection, Reverse battery polarity protection, Phase lost protection* |
Alarms |
Charger Fail, DC High, Under/Over Voltage Trip, Earth Fault*, Low Electrolyte, Battery Disconnected*, Battery Over Temperature*, Blown Fuse*, Common Alarm Relay, Common Alarm Buzzer (All alarms are user programmable) |
Metering |
Charger Voltage, Charger Current, Load Voltage, Load Current, Battery Temperature*, Battery Capacity Ratio (Meter accuracy 1%) |
Options |
DC Voltage Regulator, TCP/IP adaptor, Triphase control and shot, Cabinet lamp Temperature and humidity controller, DC distribution board |
Physical |
Well mount on free standing powder coated metal cabinet (Dimensions depend on charger output rating and associated battery requirements) |
Environmental |
-10 to 50 degree Celsius, up to 95% humidity |
Operating attitude (m) |
3000 (without dreating) |
Communication Interface |
RS232/RS485 Modbus, TCP/IP Ethernet (optional) |
DC Meter Disply (Optional) |
For display the voltage and current of charger on the panel |
MTBF/MTTR |
100000 hours/ 4hours |
Efficiency |
80-93% depending on nominal voltage and power rating |
Temperature compensation |
Programmable 3-6 mV/Cell/degree Celsius |
Audible noise |
<60 dB |
Limp home feature |
Continuous operation in the event of control failure |
Revert to factory settings |
Reinstates all original factory settings |
System |
SCR full-bridge, Intelligence charging management, fast acting fuse |